Achieving Perfect Accuracy: How CT Analyzers Can Mimic Primary Injection Results

KPM Tech Team

Workers in hard hats gather around a device in an industrial setting, intent on a screen. The mood is focused and collaborative.
Generator Bus Duct CT Testing using KPM CT/PT Analyzer.

In the world of electrical engineering, Current Transformers (CTs) are critical components used to measure high currents by producing proportional, smaller currents suitable for metering and protection. The accuracy of these transformers is paramount, especially in industrial applications, where even small errors can lead to substantial losses, safety risks, or regulatory non-compliance.


To assess the performance of CTs, two key testing methods are often used: the CT Analyzer and the Primary Current Injection Method. Both methods aim to measure the ratio error and phase error of the CT, but sometimes, their results don't match perfectly. Understanding the relevance of these methods, the reasons for discrepancies, and how to reconcile them is crucial for manufacturers and users alike.


CT Analyzers: A Vital Tool for Testing


GIS CT Testing using KPM CT PT Analyzer .

A CT Analyzer is a specialized instrument designed to test the performance of current transformers. It measures ratio error, phase shift, and other key parameters of the CT, such as burden resistance and insulation integrity.

CT Analyzers can test transformers at different loading conditions, simulate the actual operating environment, and provide quick results. These devices are especially useful in factory testing and field calibration, offering a non-invasive and relatively fast way to ensure the CT's accuracy.

Key Features of CT Analyzers:

  • Ratio Testing: Measures the ratio between primary current and secondary current.

  • Phase Error Testing: Evaluates the phase shift between the primary and secondary currents.

  • Burden Testing: Checks the load capacity of the CT under various conditions.

  • Saturation Characteristics: Tests the point at which a CT will no longer provide accurate output under high current conditions.

CT Analyzers offer a precise, controlled environment to assess a CT's accuracy under normal operating conditions. This makes them essential for factory calibration before shipping and during regular maintenance in the field.


Primary Current Injection Method: A More Direct Approach


Primary Current Injection method for CT Testing

The Primary Current Injection Method is a more traditional testing technique. In this method, actual current is injected directly into the primary windings of the CT, and the secondary current is measured. This is essentially a real-world test because it uses actual current flow, as opposed to simulated test currents generated by a CT Analyzer.

Key Advantages of Primary Current Injection:

  • Realistic Testing: Tests the CT under actual operational conditions.

  • Accurate Results: Provides data on how the CT will behave under different current levels, including its saturation point.

  • Comprehensive Testing: Allows for testing under high-current conditions, which is essential for determining the CT's performance at its maximum rated current.

This method is often used in field testing or in scenarios where high currents are involved, such as substation installations or switchgear testing. It is considered the gold standard for ensuring a CT’s real-world accuracy.


Why the Results May Not Match


Despite the value of both the CT Analyzer and Primary Current Injection Method, discrepancies between the results from these two tests are not uncommon, especially when measuring ratio errors and phase errors. Here are some reasons why this might happen:


  1. Testing Environment and Conditions:

    • CT Analyzers simulate controlled conditions that may not perfectly mimic the actual operational environment. For instance, the burden (resistance) in real-world applications might differ slightly from the values set during testing. Temperature, humidity, and electromagnetic interference can also alter the results, leading to discrepancies in the measurements.

    • On the other hand, the Primary Current Injection Method uses actual physical current flowing through the transformer, so it accounts for more complex, real-world factors that might not be captured in the analyzer's simulated environment.

  2. Saturation Effects:

    • In some cases, core saturation in a CT occurs when high current is passed through it. CT Analyzers may not always test the transformer up to these extreme saturation points, while the Primary Current Injection Method pushes the CT to its limits. This leads to potential differences in phase shift and ratio error, especially under high current levels.

  3. Measurement Accuracy:

    • While CT Analyzers are designed to measure with high precision, they may still have calibration tolerances that can lead to minor errors. In contrast, the Primary Current Injection Method often relies on analog testing equipment that may introduce other sources of error, such as instrument accuracy or human error in reading the results.

  4. Harmonics and Transients:

    • The Primary Injection Method is particularly sensitive to harmonics (distortions in the current wave) and transients (sudden changes in current). If the injected current is not perfectly sinusoidal, it may cause phase errors that are not detected in a purely analytical CT Analyzer test.

  5. Load Conditions and Burden:

    • The burden (resistance) connected to the secondary circuit plays a significant role in determining phase shift and ratio error. A CT Analyzer allows users to adjust the burden during testing, but it may not always replicate the specific load conditions under which the CT will operate in the field. Conversely, the Primary Injection Method applies real-world load directly, potentially yielding different results.


How an accurate CT Analyzer Can Match the Primary Injection Method Results



To minimize discrepancies between the two testing methods, a high-quality CT Analyzer should have several advanced features designed to emulate the primary current injection test as closely as possible:


  1. Wide Current Range: A top-tier CT analyzer should be capable of simulating a wide range of currents, from very low to high, including the saturation region. This helps to reproduce the conditions tested in the Primary Injection Method.

  2. Adjustable Burden Simulation: A CT Analyzer should allow the user to adjust the burden (secondary resistance) during the test to closely match the load conditions that the CT will experience in the field. This ensures the phase error and ratio error results reflect the real-world operational environment.

  3. Harmonics Simulation: The ability to simulate non-sinusoidal currents, such as those with harmonics, can help match the primary current injection method results more accurately, particularly in modern systems with distorted waveforms.

  4. Advanced Calibration: A good CT Analyzer must be calibrated regularly to ensure measurement accuracy that can be trusted. This includes correcting for potential sources of error that might cause discrepancies when compared to primary current injection testing.

  5. Detailed Reporting: An advanced CT analyzer should provide detailed reports, including error margins and test conditions, allowing manufacturers to correlate the analyzer results with real-world tests and adjust accordingly.


Conclusion


Both the CT Analyzer and Primary Current Injection Method are essential tools for ensuring the accuracy and reliability of Current Transformers. While discrepancies in ratio and phase errors can occur due to testing conditions, a high-quality CT Analyzer that can simulate real-world conditions effectively can provide results that closely match the primary current injection method.


For manufacturers, using a well-calibrated CT Analyzer to verify primary injection test results can lead to more accurate, reliable products, ensuring they meet the necessary standards for performance and safety. By aligning both methods, manufacturers can ensure their current transformers are ready for the demands of modern electrical systems.